Interpret Of Enjoypowers Static Var Generator SVG’s third party CQC Test Report

Interpret Of Static Var Generator SVG’s Test Report 2020

All power quality products of Enjoypowers Technology have passed the third-party test of CCIC Southern Testing Co., LTD and obtained the CQC certificate.

In order to facilitate partners to understand the performance of Enjoypowers’ power quality products, I will share the entire SVG test report with you based on the Static Var Generator SVG test report issued by CCIC-SET.

About CCIC-SET

Established in 1985, CCIC Southern Testing Co., LTD is a holding company of China Inspection and Certification Group (CCIC) and a third-party inspection and testing technical institution with an independent legal personality. He has won the “National Quality Certification Qualification Unit (CMA)”, “China National Accreditation Service for Conformity Assessment (CNAS) Accredited Laboratory”, “China Quality Certification Center (CQC) Contract Laboratory”, “TUV Rheinland Authorized Third-Party Testing” Laboratory” and other more than 20 important qualifications at Chinese and foreign qualifications.

enjoypowers svg test in CCIC-SET
enjoypowers svg test in CCIC-SET

Enjoypowers’ Static Var Generator SVG test report background

Application number: V2019CQC020018-467031

Report number: C-02101-V202008674(XG1)

Product name: SVG

Model: SinE-100S44L

Testing agency: CCIC Southern Testing Co., Ltd.

Completion Date: April 3, 2020

Applicant: Enjoypowers

Test basis standard: DL/T 1216-2013 “Technical Specification for Static Var Compensation Device for Distribution Network”

Test sample description and description

Main components

Filter capacitor, filter inductor, IGBT, DC bus capacitor, fuse, controller, fan

Operation mode

After the device is powered on, it starts automatically, and the system enters the normal working state.

Control method

The device control system collects and detects the load signal, analyzes the load-side reactive current through the control algorithm, and controls the converter module composed of IGBTs through PWM to actively send out a reactive current with the same amplitude and opposite direction as the load-side reactive current. The current offset the reactive current in the grid, thereby realizing the function of compensating reactive power.

Workplace

Pollution level PD2, the working environment temperature is -25°C-45°C, the rated power working environment temperature is 45°C, the ambient temperature is greater than 45°C, and the derating is used. The working altitude is below 2000m, when the altitude is greater than 2000m, derating is used. The relative humidity of the environment is 5%-95%, without condensation.

Working principle diagram

Electrical schematic diagram of enjoypowers AHF
Electrical schematic diagram of enjoypowers AHF

Test items and results

No. Test items Test result
1 Visual and structural inspection qualified
2 Protection class test qualified
3 Clearance and Creepage Distance Inspection qualified
4 Dielectric Strength Test Insulation resistance verification qualified
5 Power frequency withstand voltage test qualified
6 Lightning impulse test not applicable
7 AC voltage test between commutation chain terminals not applicable
8 Accuracy measurement test qualified
9 Protection test qualified
10 temperature rise test qualified
11 performance test Continuous Operating Range Test qualified
12 Voltage control test not applicable
13 Constant reactive power control test qualified
14 Reactive power tracking control test qualified
15 Power factor control test qualified
16 Step Response Test qualified
17 Loss assessment qualified
18 Harmonic test qualified
19 Output harmonic test qualified
20 Harmonic compensation test qualified
21 Continuous running test qualified
22 Noise test qualified
23 Electromagnetic Compatibility Test Radiated electromagnetic field interference test qualified
24 Fast transient disturbance test qualified
25 Burst interference test qualified
26 Electrostatic discharge interference test qualified
27 Telephone and Radio Interference Testing qualified

Important test items and results

Dielectric strength test insulation resistance verification

Results of measurements and observations:

Between phase conductors: >100MΩ

Between phase conductor and shell: >100MΩ

Dielectric strength test Power frequency withstand voltage test

The applied voltage is: 2500Vac The sample has no discharge phenomenon and no damage

The applied voltage is: 3750Vac The sample has no discharge phenomenon and no damage

Accuracy measurement test

Relative error at 100% rated inductive reactive power output

Voltage/current Display value Test value Error value
Voltage A 229 228.939 0.03%
B 229 228.687 0.14%
C 229.1 229.889 -0.34%
Current A 149.7 149.069 0.42%
B 146.2 145.995 0.14%
C 152.6 152.436 0.11%

Relative error at 100% rated capacitive reactive power output

Voltage/current Display value Test value Error value
Voltage A 236 235.245 0.32%
B 236.7 236.054 0.27%
C 236.4 236.459 -0.02%
Current A 145 144.899 0.07%
B 142 141.972 0.02%
C 148.2 148.038 0.11%

Protection test

  • The device has a power-on self-test function. When the self-test is abnormal, all operations are locked, and the alarm indicator is on.
  • The device has a synchronization signal;
  • Protection function
Protection item Test process Difference
DC bus overvoltage The overvoltage protection value of half the DC bus of the device is 390v. When the voltage of the DC bus rises to 390.25v, the device immediately reports “bus overvoltage” and stops operation, and the alarm indicator is on. <±5%
DC bus Undervoltage The overvoltage protection value of the half DC bus of the device is 300V. When the voltage of the DC bus rises to 299.8v, the device immediately reports “bus Undervoltage” and stops operation, and the alarm indicator is on. <±5%
Drive board fault Disconnect the drive cable, stop the device for protection, and the alarm indicator is on. qualified
Device over-temperature protection The NTC over-temperature protection value of the device is set to 80 ℃. When the temperature reaches 79.8 ℃, the device immediately reports an “abnormal temperature” and stops operation, and the alarm indicator is on. <±5%
AC overvoltage Set the overvoltage protection value of the device to 268v and slowly increase the input voltage. When the voltage reaches 268.9v, the device will immediately report “grid overvoltage” and stop operation, and the alarm indicator will be on. <±5%
AC Undervoltage Set the Undervoltage protection value of the device to 130v and slowly reduce the input voltage. When the voltage reaches 131.9v, the device immediately reports “grid Undervoltage” and stops operation, and the alarm indicator is on. <±5%
Overcurrent The single module overcurrent protection value is set to 160A. When the analog rapidly increases the output current to 154.6a, the device immediately reports “output overcurrent” and stops operation, and the alarm indicator is on. <±5%
Abnormal cooling system If the fan of the analog device fails, the device will immediately report “fan failure” and the alarm indicator will be on. qualified

Temperature rise test

Ambient temperature (℃): 25.3

Test current: main circuit 150A

Connecting conductor: Cross-sectional area 50㎡, The length shall not be less than 2m

Measuring point Temperature rise K Temperature rise limit K
R5 soft starter resistance 12.5 30
L2 inductance 35.7 125
F1 fuse 29.9 65
L13 inductance 24.2 125
L14 inductance 30.5 125
M4 T1 transformer 33.1 125
Rly7 relay 36.3 45
T3 transformer 34 45
T6 coil 16.7 125
C7 capacitance 20.4 45
C19 filter capacitor 16 45
U9 main chip 29.3 90
U10 main chip 30.5 90
Enclosure 10.2 20
HMI 10 20

Performance test: step response test

Step response time (ms)
0~100kVar 2.2
100 kVar ~0 2.96
0~-100kVar 4.76
-100 kVar ~0 1.84
100 kVar ~-100kVar 7.8
-100 kVar ~100kVar 3.88
enjoypowers SVG Response test waveform for step change of 0~100kvar
enjoypowers SVG Response test waveform for step change of 0~100kvar

Performance Test: Operational Efficiency

The measured loss values are as follows when operating under the conditions of rated voltage and rated current:

Set value

(kVar)

Measured active power

(kW)

loss
Allowable value Measured value
101.402 2.445 2.50% 2.41%
-100.824 2.432 2.50% 2.41%

Performance test: power factor control test

Set the device to power factor control mode, and adjust the target power factor setting value so that the device output changes from the maximum inductive reactive current to the maximum capacitive reactive current. The measured power factor data are as follows:

Power factor setting value Phase Load PF Grid PF Difference
0.9 A 0.6 0.89527 -0.52%
B 0.6 0.88876 -1.24%
C 0.6 0.87994 -2.22%
-0.9 A 0.6 0.90274 0.27%
B 0.6 0.90759 0.84%
C 0.6 0.90801 0.89%
0.9 A 0.6 0.90752 0.83%
B 0.3 0.90714 0.79%
C 0.95 0.89889 -0.12%
-0.9 A 0.6 0.91494 1.66%
B 0.3 0.89524 -0.52%
C 0.95 0.89795 -0.22%

Performance test: Output harmonic test

In the constant reactive power control mode, the rated inductive output capacity and the rated capacitive output capacity test the total harmonic current distortion rate of the output current respectively. The data are as follows:

Set value

(kVar)

THDi (%)
A B C
100 2.198 2.255 2.721
-100 2.456 2.784 2.82

Performance test: Compensated Harmonic Test

Before and after compensation, the three-phase current size, waveform, and harmonic content of each current and the total harmonic current distortion rate of the system shall satisfy the ratio of the current root mean square value after harmonic and before harmonic ≤50%.

The main circuit input is 230V, and the harmonic source emits harmonic current less than or equal to the 13th order. The harmonic current values before and after compensation are recorded by the power analyzer. The calculated ratio of the current rms value after harmonic and before harmonic is as follows:

A B C
Harmonic current value before compensation (A) 98.583 99.001 99.019
Harmonic current value after compensation (A) 18.089 18.291 17.842
The ratio of post-harmonic to pre-harmonic current rms value (%) 18.35 18.48 18.02

Performance test: Noise test

Rated load and ambient noise ≤40dB; 1m from the horizontal position of the noise source, the maximum measured noise of the device is ≤70dB.

Noise(dB)
forward back left right
54.6 50.1 49.8 52.1

Performance test: Radiated electromagnetic field interference test

Judgment criteria

Function acceptance criteria
Protect Normal performance within specified limits
Command and control
Measurement
HMI and alarms
communication

Test type: indoor type

Application site: module

Distance between sample and antenna: 3m

Polarity: H/V

Frequency range: 80MHz-2.7GHz

Test level: 10V/m

The device display and work should be normal.

Layout diagram for the test equipment

Enjoypowers SVG 80MHz-1GHz Radiated electromagnetic field interference test
Enjoypowers SVG 80MHz-1GHz Radiated electromagnetic field interference test
Enjoypowers SVG 1GHz-2.7GHz Radiated electromagnetic field interference test
Enjoypowers SVG 1GHz-2.7GHz Radiated electromagnetic field interference test

There were no dangerous or unsafe consequences during the entire test, and the EUT worked normally after the test, showing immunity to interference. meet the criteria for determination.

Performance test: Burst interference test

Judgment criteria:

Feature Acceptance Criteria
Protection Normal performance within specified limits
Command and Control Normal performance within specified limits
Measurement The performance drops temporarily during the test, and recovers after the test without losing the stored data
HMI and visual alarms Temporary reduction in performance or loss of function during the test, Self-recovery after the test, the stored data is not lost
Data communication Bit error rate may increase without loss of transmitted data
  • Application position: line-line

Test voltage: 1KV

Test polarity: +, –

Oscillation frequency: 0.1 MHz

Repetition rate: 40 times/s

Application time: 2min

The device display and work should be normal.

  • Application position: line-line

Test voltage: 1KV

Test polarity: +, –

Oscillation frequency: 1 MHz

Repeat rate: 400 times/s

Application time: 2min

The device display and work should be normal.

  • Application position: line-ground

Test voltage: 2.5KV

Test polarity: +, –

Oscillation frequency: 0.1 MHz

Repetition rate: 40 times/s

Application time: 2min

The device display and work should be normal.

  • Application position: line-ground

Test voltage: 2.5KV

Test polarity: +, –

Oscillation frequency: 1 MHz

Repeat rate: 400 times/s

Application time: 2min

The device display and work should be normal.

The following figure shows the test layout:

Enjoypowers SVG Burst interference test
Enjoypowers SVG Burst interference test

Performance test: Electrostatic discharge test

Judgment criteria:

Feature Acceptance Criteria
Protection Normal performance within specified limits
Command and Control Normal performance within specified limits
Measurement The performance drops temporarily during the test, and recovers after the test without losing the stored data
Human-Machine Interface and Visual Alarms Temporary reduction in performance or loss of function during the test, Self-recovery after the test, the stored data is not lost
Data communication Bit error rate may increase without loss of transmitted data

After the device is powered on, the following interference signals are applied:

Applied voltage value: 8kV

Discharge voltage polarity: positive, negative

Discharge method: air discharge

Implementation: Direct Discharge

Discharge times: 10 times

Time interval between two discharges (s): 1s

Application site: shell, gap and operation panel

After the test, the device displays and works normally.

Applied voltage value: 6kV

Discharge voltage polarity: positive, negative

Discharge method: contact discharge

Implementation: Direct Discharge and Indirect Discharge

Discharge times: 10 times

Time interval between two discharges (s): 1s

Application part: metal shell, coupling plate

After the test, the device displays and works normally.

The following figure shows the layout of the test equipment:

There were no dangerous or unsafe consequences throughout the test, and the EUT worked normally after the test, showing immunity to interference. meet the criteria for determination.

Conclusion

Enjoypowers focuses on the R&D and production of power quality products and provides OEM services for more than 480 partners in the world. All power quality products, including active harmonic filters and static var generators, have passed the strict testing of CQC, and have obtained CE, RoHs, and other certifications.

Selecting power quality products according to your specific requirements: Enjoypowers team is happy to assist you to select and calculate the appropriate AHF or module size and implement a power quality solution that perfectly meets your requirements.

For this, please send us your application data and contact me: [email protected], Or connect with me on LinkedIn.

Scroll to Top